Section 9—Troubleshooting
The following Troubleshooting Guide offers simple solutions to
common problems and explains the 2110’s Error Messages. Re-
view this section for a possible solution to your problem before
contacting Chromalox.
Note: For each symptom, perform correction steps in the order
listed.
22
Section 9–Troubleshooting
Symptom Probable Cause Correction Steps
Power applied, dis-
play does not light,
and controller does
not function
1. No power applied
2. External fuse open
1. Check power wiring and
fusing
2. Power down and
repower up
Display alternates
between HI and
SENS, 2110 disables
control output
1. Open sensor
2. Out of calibration
1. Check sensor wiring
2.
Check selection switches
3. To verify that control-
ler is at fault, remove
the thermocouple and
place a jumper across
the sensor terminals of
the 2110. If the display
reads approximately
ambient, then the sen-
sor is open. Replace the
thermocouple.
4. See Section 7–Calibra-
tion
Process does not
heat up
1. No power being
applied to the load
2. Load fuse open
1. Verify Load LED is ON
2. Verify the heater or fuse
is not open
3. Verify output limit is set
to 100%
4. Verify set point is
greater than process
temperature
5. Verify output wiring
Erratic operation 1. Intermittent sensor
connections
2.
Controller failure
(internal electronics)
3. External electrical
noise
1. Check sensor wiring or
substitute sensor
simulator
2. Power down and
repower up
3. Contact Chromalox