Chromalox 2110
Factory Calibration
Recovery
This procedure allows you to return the controller to its factory
calibration settings in the event it is severely out of calibration
due to poor technique or unauthorized calibration.
1. Disconnect load power.
2. Cycle the sensor selection switch twice from its original posi-
tion (TC or RTD) to the opposite position (RTD or TC) and
back to its original position. This brings back the factory cali-
bration and deletes the manual calibration settings.
20
Section 7–Calibration
When calibrating the 2110
1. You must have a sensor simulator to calibrate the 2110 controller.
Substitute a precision sensor simulator (Thermocouple simulator
or resistance simulator box) for sensor inputs.
2. Disconnect load power to prevent damage to the process or load.
3. Calibrate RTD inputs using copper (Cu) wire. Calibrate thermo-
couple inputs using thermocouple extension wire of the same
type as the thermocouple you are calibrating.
4. Allow the controller to warm up with the appropriate sensor simu-
lator connected for at least one hour prior to calibration.
5. To access the calibration menu, you need level C (736) security.
Sensor Calibration:
1. Set the 2110 selection switch to RTD or TC. If TC is selected,
then set the selection switch to J or K.
2. Connect the sensor simulator to the sensor input terminals.
3. Set the simulator to the low value of the sensor selected J TC
(-100°F), K TC (-100°F), RTD (-200°F or 48.46W).
4. Go to the CALS parameter on the 2110. The display will toggle
between CALS and inLo.
5. Wait 30 seconds for the electronics to fully stabilize. Press .
Dashes will appear in the display while the controller calibrates
the low end of span.
6. When the controller prompts inHi in the display, adjust the sensor
simulator to the high end of the selected sensor span.
J TC (1400°F), K TC (2400°F), RTD (1000°F or 293.49W).
7. Wait 30 seconds for the electronics to fully stabilize. Press .
Dashes will appear in the display while the controller calibrates
the high end of span. When finished, the controller will display
donE.
8. Calibration is complete.
Calibration
continued