DATESALESREFERENCEDIVISION SECTIONChromalox®(Supersedes PF455-2)PF455-3DH161-562766-001FEBRUARY, 20014Chromalox Electric Airduct Heaterswith Fintube H
GENERALLimitations: Ductwork must be in accordance with one of the fol-lowing: Standards of the National Fire Protection Association forthe installati
7. Installation in duct larger than heater. For installation where theduct dimensions exceed the insert type heater dimensions, thearea beyond the hea
MOUNTINGMultiple Duct Heaters: Up to six duct heaters may be combinedinto a heating bank as shown in Figure 15. When called for onorder, brackets will
Mounting Procedure — DHIF(Flanged heaters with control box)1. At heater location, cut out a section of duct, or a new con-struction lay out duct work
WIRINGWIRING DIAGRAMRENEWAL PARTS IDENTIFICATION1. Connect heater only to the voltage, frequency and phase spec-ified on the nameplate.2. All wiring s
O O O O - O O O - 0 0 H X 0 0 0 W - X 0 0 . 0 0 D - 0 0 0 V 0 0 P - 0 0 0 . 0 kW000.0kW, (16kW/Ft.2MAX.)Phase: 1P = Single Phase’ 3P
2150 N. RULON WHITE BLVD., OGDEN, UT 84404Phone: 1-800-368-2493 www.chromalox.comLimited Warranty:Please refer to the Chromalox limited warran