Chromalox 2104 Dokumentacja Strona 59

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 58
54 Chromalox 2104 Technical Manual
Control Loop Protection Alarm (continued)
If the control loop does not respond with a change
in the process variable of 0.25% of span (3.75°F for
a J thermocouple) within the programmed loop
time, a Loop Error will result and the control output
will turn off. The error will be indicated by the
lower display flashing LOOP and Loop Alarm Output
(Output #3, #4, or #5 as selected on the menu) will
be activated. The Loop Alarm is cleared by pressing
RESET.
Press RESET
to clear Loop Alarm
LL
LL
L
OOPOOP
OOPOOP
OOP
OO
OO
O
FFFF
FFFF
FF
AUX ▲▼
RESET
Warning
The CLP is not a substitute for safety shutdown
devices such as flow switches or overtemperature
monitors. The CLP Alarm responds to specific
conditions that may provide early warning of system
loop failures or aid in troubleshooting failures.
Przeglądanie stron 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 107 108

Komentarze do niniejszej Instrukcji

Brak uwag